DEFECTS REPORT FOR PLOT 1 NEW TOWN INDUSTRIAL ESTATE CERTIFICATE NUMBER
WIRING SYSTEMS
W1 The wiring installation comprises of PVC insulated cables, and where inspected were found to be in a good serviceable condition.
EARTHING SYSTEM
E1 The earthing system does not comply with the current wiring regulations.
E3 The Back boxes are not connected to the earthing conductor correctly.
Code (1) Location: In stores
E6 No mechanical protection has been provided for the earth electrode circuit.
Code (1) Location: Mains point
DISTRIBUTION BOARDS
DB1 The distribution board duties have not been marked up.
Code (2) Location: DB2, DB7 and DB9
DB2 The circuit breakers are incorrectly sized.
Code (1) Location: In DB2
DB3 The distribution board is showing signs of overheating.
Code (1) Location: DB7
DB4 The distribution board has phase barriers missing.
Code (1) Location: DB9
ACCESSORIES
ACC1 The wiring accessories are showing signs of overheating.
Code (1) Location: In office 4
ACC2 The accessories are cracked
Code (1) Location: In canteen
ACC6 No grommets has been fitted in the accessories boxes.
Code (1) Location: In all offices
TRUNKING SYSTEM
T1 The trunking lid is missing.
Code (1) Location: In workshop by roller-shutter doors
T2 Cables are hanging out of the trunking.
Code (1) Location: adjacent to canteen entrance
T3 The trunking has been damaged.
Code (1) Location: At entrance to welding shop
CONDUIT SYSTEM
CON1 The conduit has been damaged.
Code ( 1 ) Location: In welding shop
CON2 The conduit is not correctly supported.
Code ( 1 ) Location: In paint room
EMERGENCY LIGHTING
El1 The emergency lighting fitting did not light up on test.
Code ( 1 ) Location: Office 1
EL2 The emergency lighting fitting failed to maintain light for three hours on test
Code ( 1 ) Location: Office 1 and 2
EL3 The emergency lighting fitting is broken.
Code ( 1 ) Location: In office 1