Back to previous page

DEFECTS REPORT FOR PLOT 1 NEW TOWN INDUSTRIAL ESTATE CERTIFICATE NUMBER

 

WIRING SYSTEMS

W1 The wiring installation comprises of PVC insulated cables, and where inspected were found to be in a good serviceable condition.


EARTHING SYSTEM

E1 The earthing system does not comply with the current wiring regulations.

E3 The Back boxes are not connected to the earthing conductor correctly.

Code (1) Location: In stores


E6 No mechanical protection has been provided for the earth electrode circuit.

Code (1) Location: Mains point


DISTRIBUTION BOARDS

DB1 The distribution board duties have not been marked up.

Code (2) Location: DB2, DB7 and DB9

DB2 The circuit breakers are incorrectly sized.

Code (1) Location: In DB2

DB3 The distribution board is showing signs of overheating.

Code (1) Location: DB7

DB4 The distribution board has phase barriers missing.

Code (1) Location: DB9

ACCESSORIES

ACC1 The wiring accessories are showing signs of overheating.

Code (1) Location: In office 4

ACC2 The accessories are cracked

Code (1) Location: In canteen

ACC6 No grommets has been fitted in the accessories boxes.

Code (1) Location: In all offices


TRUNKING SYSTEM

T1 The trunking lid is missing.

Code (1) Location: In workshop by roller-shutter doors

T2 Cables are hanging out of the trunking.

Code (1) Location: adjacent to canteen entrance

T3 The trunking has been damaged.

Code (1) Location: At entrance to welding shop


CONDUIT SYSTEM

CON1 The conduit has been damaged.

Code ( 1 ) Location: In welding shop

CON2 The conduit is not correctly supported.

Code ( 1 ) Location: In paint room


EMERGENCY LIGHTING

El1 The emergency lighting fitting did not light up on test.

Code ( 1 ) Location: Office 1

EL2 The emergency lighting fitting failed to maintain light for three hours on test

Code ( 1 ) Location: Office 1 and 2

EL3 The emergency lighting fitting is broken.

Code ( 1 ) Location: In office 1


Back to previous page